FT522 Usage Monitor
Instructions
LT-10829-A
Page 1 of 4
General Information
Specifications
Power 115/220 VAC, 50/60 Hz,
12-24 VDC
Temperature 32° - 130° F (0° - 55° C)
Enclosure Precision cast aluminum,
NEMA 4X
Alarm Outputs Two Form C SPDT relay,
115 VAC 5A max
Max Pulse Output 100 mA at 60 VDC
Memory Type Non-volatile EEPROM
auto-backup
Sensor Power 12 VDC, 10 mA
Totalizer 8 digit
Rate Display 5 digit
Volume Units Gallons, cubic feet, cubic
meters
Time Units Minutes, hours
Analog Output 4-20 mA, 0-10 VDC,
opto-isolated
Sensor Input Open collector current sink,
ESD protected
Max Input Frequency 1,000 Hz
Shipping Weight 7 lbs
The FT522 is a flowmeter monitor with added output and
alarm features. It is designed for use with SeaMetrics
flow meters and sensors, as well as other units which
have a pulse or frequency output. It displays flow rate
and total in large digits on an easily-read backlit display.
Units are user selectable between gallons, cubic feet,
and cubic meters.
The primary output of this unit is a user-set alarm relay
which signals excess total flow within a given time pe-
riod (up to 48 hours). This is typically used to detect an
overly high usage level in a cooling tower or potable water
application. The dual relays can be connected to an
alarm, autodialer, or any other switch-controllable
device.
In addition to the usage alarm, the FT522 has analog
output (4-20 mA, 0-10 VDC) and programmable pulse
output. These can be used for data logging or to provide
proportional chemical feed, using an externally-controlled
metering pump.
Features
Relay 1
Relay 2
Pulse
Output
0:00:00
0 GAL
ELAPSED
Set
Resume
Stop
Easy-read
backlit display
Remote control terminals
(inside housing)
Rugged cast aluminum
housing
(wall or panel mount)
Choice of
rate/volume units
Alarm output
indicator LED
Accessible
control buttons
Comments to this Manuals